| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys GV4
|
|
| device short name |
GV4L
|
|
| product or component type |
Circuit breaker
|
|
| device application |
Motor protection
|
|
| poles description |
3P
|
|
| utilisation category |
Category A
|
|
| trip unit technology |
Magnetic
Electronic |
|
| protection type |
Short-circuit
|
|
| [In] rated current |
50 A
|
|
| breaking capacity |
Icu 100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 Icu 8 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Ics] rated service breaking capacity |
100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| Magnetic setting range |
300…700 A
|
|
| control type |
Rotary handle
|